반응형
EXPANSION & CONTRACTION CALCULATION:
v BLACK CARBON STEEL PIPE: - ASTM / A53 / SCH 40.
v PIPING THERMAL GROWTH:-
1. THERMAL GROWTH COEFFICIENT = 0.0000125 mt / mtº c
2. OPERATING TEMPERATURE = 5.5º C
3. TEMP. AT TIME OF INSTALLATION = 48º C
EXPECTED THERMAL GROWTH (DL) = L* δ * DT mt / mtº c
v L = LENGTH OF THE PIPE INSTALLED IN THE BRIDGE. (38 MTR)
v DT= (DIFF.BETWEEN TEMP.AT TIME OF INSTILL. --- OPERA.TEMP).
v δ = THERMAL GROWTH CO-EFFICIENT (0.0000125 mt / mtº c).
EXPECTED THERMAL GROWTH (DL) = L* δ * DT mt / mtº c
= 38* 0.0000125* (48-5.5)
= 0.02019 mt / mtº c
= 20.19 mm / mtº c.
We use victaulic coupling (flexible coupling style 077).
v Max.available movement per style 77 flexible coupling is 6.4mm with cut grooved pipe for 10" dia.
v Safety 25%
v Available movement per coupling = 6.4* 0.75 = 4.8 mm.
ý Number of coupling's = 20.19 / 4.8
=4.20 = 4 NOS